Specification of FZM-1 Zone Module for Detector
• Supports compatible two-wire smoke detectors.
• Supervises IDC wiring and connection of external power source.
• High noise (EMF/RFI) immunity.
• SEMS screws with clamping plates for ease of wiring.
• Direct-dial entry of address: 01 – 159 on FlashScan loops, 01 – 99 on CLIP loops.
• LED flashes during normal operation; this is a programma- ble option.
• LED latches steady to indicate alarm on command from control panel.
The FZM-1(A) Interface Module is intended for use in intelli- gent, addressable systems, where the individual address of each module is selected using built-in rotary switches. This module allows intelligent panels to interface and monitor two- wire conventional smoke detectors. It transmits the status (nor- mal, open, or alarm) of one full zone of conventional detectors back to the control panel. All two-wire detectors being moni- tored must be UL compatible with the module. The FZM-1(A) can be used to replace MMX-2(A) modules in existing sys- tems.